Advice · Wiring and code upgrades
Grandfathered electrical: how far does it go?
An installation done according to the Code of its time does not have to follow today's Code. Until the day it is modified. Here is what the Régie du bâtiment du Québec says, with examples.
The Code is not retroactive
The Régie du bâtiment du Québec (RBQ) wrote it in a technical interpretation published in April 2012: the current Code is simply not retroactive. To judge an installation done in the past, the Code of that time is the reference.
This is what is called an acquired (grandfathered) right. An installation that met the Code in force on the day it was done does not have to be redone every time the Code changes.
One limit, though: Quebec's Safety Code, which also applies to existing installations, keeps a few more stringent requirements that apply whatever the year. The first is a Class A GFCI for the bathroom outlet within 1.5 m of the tub or shower, for hot tubs and around pools (sections 10.1 and 22).
A note on the date: this RBQ text is based on Chapter V, Electricity, of the 2010 Construction Code. The chapter has been updated since, but the principle explained here is the one the RBQ published.
“The current Code is simply not retroactive.”
Régie du bâtiment du Québec, “Mesures différentes et droits acquis” (alternative measures and acquired rights), April 2012
Replacing: the acquired right remains
According to the RBQ, acquired rights still apply when you only replace a device with another one that is similar. A worn outlet replaced with an outlet of the same kind, for example.
The RBQ adds a condition: you must still make sure the existing characteristics will not be made worse.
For aluminum wiring, technical bulletin BTI-013 (February 2019), distributed by the CMEQ, also states that 15 A replacement outlets and switches connected to existing aluminum circuits must be marked CO/ALR. A standard Decora outlet cannot be connected to an aluminum conductor.
- Similar replacementThe acquired right remains, provided the existing condition is not made worse.
- Outlet on an aluminum circuitThe 15 A replacement outlet must be marked CO/ALR.
Modifying: the Code in force applies
Everything changes as soon as the installation is modified. The RBQ sums it up: if modification work is done on the part of the installation concerned, the acquired right becomes a duty to meet the requirements of the Code in force at the time of the work.
The rule targets the modified part. The rest of the installation, if it is not touched, keeps its acquired right.
Electrical work is reserved by law for an electrical contractor, who is responsible for the work. The CMEQ recommends written, detailed quotes: the work, the materials and the cost before taxes.
In one sentence
What is not touched, or is replaced with something similar, keeps its acquired right; what is modified follows the Code in force.
Want to know for sure?Request your quote: same-day reply before 2 p.m., on weekdays.
An example: the space in front of the panel
The RBQ gives a concrete example. Under section 2-308 of the 2010 Code, a new panel required 1 m of clearance in 2012.
That new panel may sit near an existing panel with only 915 mm of clearance, or 36 inches: the compliant value at the time. The existing panel is considered compliant with the Code of its time; the new one, with the same clearance, would not be.
In other words, two neighbouring panels can follow two different rules, depending on the year each was installed.
- Existing panel915 mm of clearance: compliant with the Code of its time.
- New panel1 m of clearance required by the 2010 Code.
When the Code cannot be followed: the alternative measure
Sometimes a project cannot meet the Code in force, for example for lack of space. The RBQ then describes two paths: change the project, by choosing another location or modifying the building, or request an alternative measure.
In a request for an alternative measure, it is up to the applicant to present the substitute measures and justify the proposed methods. The RBQ may accept, or refuse, the proposed solutions on its own terms. A compromise then makes up for the loss of the acquired right.
Not to be confused
The acquired right protects what exists. The alternative measure is a request, made to the RBQ, to depart from the Code in force.
The case of aluminum wiring
Aluminum conductors were never prohibited by the Code, bulletin BTI-013 points out. Aluminum wiring installed according to the Code of its time therefore keeps its acquired right, as long as it is not modified.
Insurers are often the ones asking for a correction. Ask your insurer, in writing, which repair they accept, then send us their request.
Two repairs are possible: correct every connection and keep the aluminum, or replace the wiring with copper. Either way, the work follows the Code in force at the time it is done.
Take stock
Our compliance inspection: $499.99 plus taxes, on-site visit and signed report included.
Request a quote
Fill in these few fields: your request goes straight to our team. Add photos if you have them, of the panel, an outlet or a cable marking: they help us prepare your quote.
- Same-day reply before 2 p.m. on weekdays
- A firm price, in writing, valid for 30 days
- No payment, no commitment
Would you rather talk to someone? 438 805-9862
Frequently asked questions
Is the electrical Code retroactive?
No. According to the RBQ, the current Code isn't retroactive: an installation is judged by the Code in force when it was done. The Safety Code keeps a few more stringent requirements, such as the GFCI near the tub or shower.
Does replacing an outlet make me lose my acquired right?
No, if the new one is similar and does not make the existing condition worse, says the RBQ. On an aluminum circuit, the 15 A replacement outlet must be marked CO/ALR.
When is an acquired right lost?
When the part of the installation concerned is modified: it must then meet the Code in force at the time of the work.
Does my old panel need 1 m of clearance?
An existing panel installed with 915 mm, the rule of the time, is considered compliant with the Code of its time. In the RBQ's example (2010 Code), a new panel needed 1 m.
Does aluminum wiring have an acquired right?
It was never prohibited by the Code. Installed according to the Code of its time, it keeps its acquired right as long as it is not modified.
What is an alternative measure?
A request to the RBQ to depart from the Code in force, with justified substitute measures. The RBQ may accept or refuse it, on its own terms.
Sources
- Safety Code (chapter B-1.1, r. 3), Chapter II, Electricity, sections 10.1 and 22, LégisQuébec (up to date as of July 1, 2026; in French)
- Régie du bâtiment du Québec, “Mesures différentes et droits acquis” (alternative measures and acquired rights), technical interpretation published on April 2, 2012 (sections 5.01 and 5.02 of Chapter V, Electricity, of the 2010 Québec Construction Code)
- Technical installation bulletin BTI-013, « Jonction des conducteurs en aluminium », 3rd issue, February 2019 (distributed by the CMEQ, in French)
- CMEQ, « Travaux d'électricité : faire le bon choix pour sa sécurité ! » (December 2020, in French)