Advice · Wiring and code upgrades
GFCI outlet : where is it required ?
Bathroom, hot tub, pool: a GFCI cuts the power as soon as current leaks to ground. Here is where Quebec's Safety Code requires one, even in an older home, with the section to back it up.
Does this outlet need protection?
Where is the outlet ?
Pick a location: the rule and its source appear here.
Class A GFCI required, even in an older home.
Quebec's Safety Code requires it for a bathroom outlet installed within 1.5 m of the bathtub or shower stall, whatever the age of the home. Two exceptions: an outlet combined with an isolating transformer, and the washing machine outlet on the wall behind it, 600 mm or less from the floor.
Safety Code, sections 10.1 and 22, 5°
To be checked on site for your work.
Sinks are not in section 22 of the Safety Code. For electrical work, the rule is in the Canadian Electrical Code, a paid text. One reference point: in 2018, the RBQ reminded farm building owners that outlets within 1.5 m of any sink or basin had to be protected by a Class A GFCI, under the Code then in force.
RBQ, reminder of January 17, 2018 (rule 26-700 11) of the Code then in force)
Class A GFCI required, even in an older home.
Quebec's Safety Code requires it for hot tubs, whirlpools and hydromassage bathtubs. Like the bathroom rule, it applies whatever the age of the installation.
Safety Code, sections 10.1 and 22, 4°
Class A GFCI required, even in an older home.
Quebec's Safety Code requires it for electrical equipment immersed in a pool's water, and for equipment within 3 m of the pool's inside walls that is not separated from it by a wall, partition or fence.
Safety Code, sections 10.1 and 22, 1° and 3°
No arc-fault protection required.
According to the RBQ's training on the 2018 edition of Chapter V, kitchen counter outlet circuits are among the exceptions to arc-fault protection. For an outlet close to the sink, see the sink case.
RBQ, training on Chapter V (2018 edition)
Arc-fault protection when work is done.
The Code requires arc-fault protection on many of the circuits that supply outlets in a dwelling, the RBQ explains; the 2026 Code keeps it, in rule 26-658. Adding an outlet to an old circuit that has none ? You don't have to protect the whole circuit if the first outlet added is an arc-fault outlet. A protected circuit has at most 10 outlets.
RBQ, training on Chapter V; Construction Code, rule 26-658 3) and 4) (2026)
Exceptions to arc-fault protection.
A circuit dedicated to a refrigerator is exempt, according to the RBQ's training on the 2018 edition. In the 2026 Code, the single outlet of a sump pump, a sewage pump or electro-medical equipment is too, if it bears a clearly visible, legible and permanent marking saying so, and its circuit supplies no other outlet.
RBQ, training on Chapter V (2018 edition); Construction Code, rule 26-658 1) b) (2026)
To be checked on site.
The detailed rules for outdoor outlets are in the Canadian Electrical Code, a paid text we don't quote from memory. Public texts say this: outdoor outlets easily reached from the ground have at least one circuit of their own, and the 120 V (5-20R) outlet used to charge a car, installed outdoors less than 2.5 m above finished ground, must be protected by a Class A GFCI. Near a pool or hot tub, the rules for those cases apply.
Construction Code, rules 26-656 f) and 86-306 2) (2026)
This tool sums up the rules published by the Government of Quebec and the Régie du bâtiment du Québec (RBQ). It does not replace an inspection: an electrician looks at where each outlet is, what already protects it and what the Code in force says for your work.
What a GFCI outlet does
GFCI stands for ground fault circuit interrupter (DDFT in French). The Office québécois de la langue française defines it as a device that automatically cuts power to a circuit when it detects a leak to ground. To spot it, the entry adds, it constantly calculates the difference between the incoming current and the ground current.
A leak is current heading to ground by a path other than the circuit's wires. The GFCI detects it and cuts the circuit. Ontario's Electrical Safety Authority (ESA) puts it its own way: a faulty GFCI increases the risk of electric shock.
It can sit in a GFCI outlet, which has its own test button, or at the start of the circuit.
The words
DDFT in French, GFCI in English in Canada : it's the same device. Quebec's texts speak of a “Class A ground fault circuit interrupter”.
A useful note if your inspection report flags ungrounded outlets: a GFCI at the start of the circuit protects people, but the outlet stays ungrounded. Replacing the cable with grounded copper fixes the problem at its source.
Even in an older home: the Safety Code
In electrical work, an installation is generally judged by the Code of its time. That's the grandfathering principle: what you don't modify doesn't have to follow every new Code.
Quebec's Safety Code, which applies to every electrical installation covered by the Building Act, including existing ones, sets a limit to that principle. Its section 10.1 says an installation must comply with the requirements that applied when it was built, “subject to the more stringent requirements” of the same chapter. And those more stringent requirements, in Division IV, start with the GFCI.
Section 22 of the Safety Code requires a Class A ground fault circuit interrupter in five cases, whatever the age of the home :
“ Subject to the more stringent requirements of this chapter, an electrical installation must comply with the regulatory requirements that applied when it was built. ” (our translation)
Safety Code, section 10.1 (up to date as of July 1, 2026)
- BathroomThe outlet within 1.5 m of the bathtub or shower stall.
- Hot tub and hydromassageHot tubs, whirlpools and hydromassage bathtubs.
- In the poolElectrical equipment immersed in a pool's water.
- Around the poolEquipment within 3 m of its walls, with no wall, partition or fence in between.
- Speaker soundThe amplifier connected to speakers submerged in a pool.
In the bathroom, two outlets are exceptions: one combined with an isolating transformer, and the washing machine outlet, on the wall behind it, 600 mm or less from the floor.
The rule isn't new. Section 22 has existed since 2002; it was amended in 2018, for the bathroom, then in 2026, to specify “Class A” and replace “therapeutic bath” with “hot tub, whirlpool”.
When work is done: the Construction Code
As soon as work is done, Chapter V, Electricity, of the Construction Code applies to the part affected. Since March 26, 2026, it has been based on the Canadian Electrical Code, 25th edition (CSA C22.1:21), with Quebec's own amendments.
The RBQ set a transition period: the previous version of the chapter can still be used if the work began before October 17, 2027.
For GFCIs, the 2026 Code covers, for example, the 120 V (5-20R) outlet used to charge a car: installed outdoors less than 2.5 m above finished ground, it must be protected by a Class A GFCI. For sinks, the RBQ reminded farm building owners in 2018 that outlets within 1.5 m of any sink or basin had to be, under the Code then in force.
What we don't quote
The full text of the Canadian Electrical Code is not free. Rules that don't appear in a public Quebec text, we check on site rather than quote from memory.
The 2026 Chapter V also contains circuit rules that affect outlets: at least one circuit for outdoor outlets easily reached from the ground, and at least one circuit reserved for the outlets of a house's garage or carport.
Want to know for sure?Request your quote: same-day reply before 2 p.m., on weekdays.
The other protection: arc-fault (AFCI)
The GFCI has a cousin: arc-fault protection, also called AFCI (DDFA in French). It targets electrical arcs in circuits. The RBQ explains that the Code requires it on many of the circuits that supply outlets in a dwelling; the 2026 Code keeps this protection, in rule 26-658.
It comes in two forms: a combination arc-fault breaker, right in the panel, or an arc-fault outlet, installed further along the circuit, under certain conditions.
A few circuits are exempt, according to the RBQ's training on the 2018 edition: outlets near sinks in bathrooms and washrooms, the circuit dedicated to the refrigerator, kitchen counter outlets, circuits that supply only outlets above 120 V, and the marked outlet of a sump pump.
- Old circuit without arc-faultYou want to add an outlet to it.
- First outlet addedAn arc-fault outlet: no need to protect the whole circuit.
- At most 10 outletsOn a circuit with arc-fault protection.
Test your GFCI outlet every month
A defective GFCI outlet can be spotted with its test button, ESA explains. It advises testing GFCI outlets every month, or as the manufacturer instructs.
The test uses the outlet's TEST button. If the power stays on after you press it, the GFCI is defective. According to ESA, defects are more common in older products.
A defective GFCI is replaced by an electrical contractor. In Quebec, the law reserves this work for an electrical contractor, whether or not you own the home.
- Press TESTEvery month, or as the manufacturer says.
- The power should cutThe GFCI is doing its job.
- Power stays on ?The GFCI is defective: have it replaced.
Have your outlets checked
Not sure whether your outlets are protected, or by what ? Our compliance inspection checks, among other things, outlet polarity and GFCI protection where required, with a signed report. It costs $499.99 plus taxes.
If you're renovating, our code upgrade installs the protections the Code requires, GFCI and AFCI, wherever it calls for them.
In one sentence
Bathroom near the tub, hot tub, pool : a Class A GFCI, whatever the age of the home.
Request a quote
Fill in these few fields: your request goes straight to our team. Add photos if you have them, of the panel, an outlet or a cable marking: they help us prepare your quote.
- Same-day reply before 2 p.m. on weekdays
- A firm price, in writing, valid for 30 days
- No payment, no commitment
Would you rather talk to someone? 438 805-9862
Frequently asked questions
Is a GFCI outlet required in a bathroom?
Yes, for the outlet within 1.5 m of the tub or shower: Quebec's Safety Code requires a Class A GFCI, even in an older home. Two exceptions: isolating transformer, washing machine outlet behind it.
Is my older home grandfathered for GFCIs?
Not for the bathroom, hot tub and pool. The Safety Code makes the GFCI a more stringent requirement, which applies whatever the age of the installation (sections 10.1 and 22).
What's the difference between DDFT and GFCI?
None: DDFT is the French term, GFCI the English term in Canada. Quebec's texts speak of a Class A ground fault circuit interrupter.
How do I test a GFCI outlet?
Press its TEST button: the power should cut. If it stays on, the GFCI is defective. ESA advises doing this test every month, or as the manufacturer says.
Does a GFCI replace grounding?
No. Installed at the start of an ungrounded circuit, it protects people, but the outlet stays ungrounded. Rewiring in copper fixes the cause.
GFCI or AFCI: which one for a bedroom?
When work is done, arc-fault protection (AFCI): the Code requires it on many of a dwelling's outlet circuits, the RBQ explains. The GFCI mainly targets places near water.
Sources
- Safety Code (chapter B-1.1, r. 3), Chapter II, Electricity, sections 10.1 and 22, LégisQuébec (up to date as of July 1, 2026; in French)
- Gazette officielle du Québec, March 11, 2026, Order 235-2026 (Regulation amending the Safety Code; in French)
- Gazette officielle du Québec, March 11, 2026, Order 236-2026 (Regulation amending the Construction Code, Chapter V, Electricity; in French)
- RBQ, “Bâtiments agricoles : rappel des exigences en électricité”, January 17, 2018 (in French)
- RBQ, training on the main changes to Chapter V, Electricity, of the Construction Code (transcript, in French)
- RBQ, “Prolongation de la période transitoire en bâtiment et en électricité”, August 26, 2026 (in French)
- Office québécois de la langue française, Grand dictionnaire terminologique, “disjoncteur différentiel de fuite à la terre” (2014, in French)
- ESA (Ontario), Homeowner Electrical Safety Handbook, “Inside the home” (French edition)
- CMEQ, « Travaux d'électricité : faire le bon choix pour sa sécurité ! » (December 2020, in French)