Advice · Aluminum wiring

How to tell if your house has aluminum wiring

The year your house was built is a first clue. The marking printed on the cable jacket gives the answer. Here is where to look, without opening the panel or the boxes.

Was your house built in those years?

In the mid-1960s, copper was scarce and expensive. Builders then used aluminum not only on large circuits such as those of the dryer and the range, but also on ordinary 15 and 20 amp circuits: outlets, lights, switches.

According to technical bulletin BTI-013, distributed by the CMEQ, a large number of houses were wired with aluminum between 1965 and 1974. Between 1974 and 1980 there were fewer: production of 12 and 10 AWG aluminum wire was dropped around 1975 or 1976, as demand kept falling.

The year of construction is not enough. The U.S. Consumer Product Safety Commission (CPSC) points out that aluminum wiring is also found in additions and in circuits redone during that period. A house from the 1950s can therefore have it in a room added in 1970.

  1. Before 1965Unlikely on ordinary circuits, according to the CPSC.
  2. 1965 to 1974A large number of houses wired with aluminum.
  3. 1974 to 1980Fewer houses; 12 and 10 AWG production ends around 1975 or 1976.
  4. 1975New standards: outlets and switches marked CO/ALR.

Read the marking on the cable jacket

Almost all household aluminum wiring was installed as plastic-sheathed cable, the same kind of cable used for copper. From the outside, nothing tells them apart at first glance. The difference is written on the jacket.

Look for a visible length of cable: unfinished basement, garage, attic, between the joists. On one side of the jacket, letters are printed or embossed, repeated every few feet. If you read “AL” or “ALUMINUM”, the wires in that cable are aluminum.

Embossed letters are hard to read under direct light. The CPSC suggests shining a flashlight across the jacket at a low angle: the shadow brings out the marking.

Read the whole marking. The words “CU-clad” or “Copper-clad” next to “AL” mean copper-coated aluminum wire: a different product, not covered by the repairs the CPSC describes.

What not to doWhen there is a sign of a problem, the CPSC says it in capital letters: do not try to do it yourself; you could be electrocuted, or make the problem worse. Our advice for reading the jacket safely:

  • Do not remove the electrical panel cover.
  • Do not open outlet or light fixture boxes.
  • Do not pull on a cable to read it better.

What outlets and switches tell you

The Code requires any device connected to aluminum wire to be approved for that use and marked accordingly. For 12 and 10 AWG wire, the marking is “CO/ALR” or “Cu/Al”, depending on the device.

The CO/ALR marking has existed since 1975. It identifies outlets, switches and connectors made to stricter standards, designed to hold up better with aluminum. BTI-013 notes that from July 1975 to September 1978, a very large number of outlets were replaced.

A CO/ALR outlet is therefore a clue, not proof: the electrician who installed it was probably thinking of aluminum, but may have put it on copper. Conversely, an ordinary Decora outlet is approved for copper only; if it is connected to aluminum, that connection needs to be redone.

A silver screw proves nothing

White-metal terminals approved Cu/Al are not aluminum: they are an alloy compatible with both copper and aluminum. The colour of a screw or terminal does not tell you what metal the wire is.

The number on the jacket: 12 or 10

The jacket marking also gives the wire size, in AWG. The smaller the number, the bigger the wire. The ordinary circuits of an aluminum-wired house are 12 or 10 AWG: the CPSC refers to appliances connected “directly to No. 12 or No. 10 AWG aluminum branch circuit wiring”.

This is no accident. The Code sets 12 AWG as the smallest size allowed for an aluminum conductor, compared with 14 AWG for copper.

  • “12” or “10” with “AL”An aluminum outlet or lighting circuit from that period.
  • “14” without “AL”A copper cable: the Code does not allow aluminum smaller than 12 AWG.

Want to know for sure?Request your quote: same-day reply before 2 p.m., on weekdays.

Dryer and range: a different case

Before the mid-1960s, aluminum was used for a few high-power circuits, such as those of the dryer and the range. Aluminum is allowed there, as everywhere else. For stranded aluminum conductors, meaning made of several strands, the Code requires a joint compound at every connection, unless the connector is approved and marked for use without it.

For a dryer or range fed with aluminum, the receptacle must be approved for aluminum and marked Cu/Al. A large aluminum cable is therefore not what this guide is about. What we are looking for are the small wires of outlets, lights and baseboard heaters.

Baseboard heaters too

BTI-013 reports failures in baseboard heaters connected with ordinary twist-on connectors. If your house has aluminum wiring, the baseboard heater connections are part of what the electrician checks.

Was aluminum wiring banned?

No. Bulletin BTI-013 says so plainly: aluminum conductors have never been prohibited by the Code, and the idea that they are banned in homes is false. Past incidents were often caused by incorrect installation.

Ontario says the same: its Electrical Safety Code permits the installation of aluminum wiring. Ontario's Electrical Safety Authority (ESA) adds that it is safe if its connections are made properly, without damaging the wire.

What disappeared were the small wires: production of 12 and 10 AWG aluminum stopped around 1975 or 1976. And the Code is not retroactive: an existing installation is judged by the Code of its time, as long as no work is done on it.

“Aluminum conductors have never been prohibited by the Code.”

Technical bulletin BTI-013, February 2019

See what it means for your insurer

You think you have it: what comes next

The CPSC warns that failing aluminum connections seldom give easy-to-see warning signs. Some signs still call for a check without delay, whether the wiring is copper or aluminum: flickering lights, an outlet or switch plate that is hot to the touch, a circuit that no longer works, a smell of burning plastic near an outlet.

To confirm, call an electrician. In Quebec, the law requires an electrical contractor for this work, whether or not you own the home. The electrician does the check for you, with no risk to you, and tells you what was found.

Then two repairs are possible: fix every connection and keep the aluminum, or replace the wiring with copper. The code compliance inspection takes stock before you choose: $499.99 plus taxes, site visit and signed report included.

  • Pigtailing: $7,500 up to 70 outlets, before taxes
  • Copper rewiring: one room a day
  • Code compliance inspection: $499.99 plus taxes
Have my house checked

See the two ways to deal with aluminum wiring

Request a quote

Fill in these few fields: your request goes straight to our team. Add photos if you have them, of the panel, an outlet or a cable marking: they help us prepare your quote.

  • Same-day reply before 2 p.m. on weekdays
  • A firm price, in writing, valid for 30 days
  • No payment, no commitment

Would you rather talk to someone? 438 805-9862

Frequently asked questions

How can I tell if my house has aluminum wiring?

Read the marking printed on the jacket of a visible cable, in an unfinished basement, a garage or an attic. “AL” or “ALUMINUM” means the wires are aluminum. If no cable is visible, have an electrician confirm it.

Which construction years are involved?

Mostly 1965 to 1974, and in smaller numbers until 1980. An older house can also have it in an addition or a circuit redone during that period.

Is aluminum wiring banned in Québec?

No. According to bulletin BTI-013, distributed by the CMEQ, aluminum conductors have never been prohibited by the Code. Connections must be made with devices approved for aluminum.

When did they stop installing it?

Production of 12 and 10 AWG aluminum wire, the size used for outlets and lights, was dropped around 1975 or 1976, according to BTI-013.

Does an outlet marked CO/ALR mean I have aluminum?

It is a clue, not proof. These outlets have existed since 1975, but they also accept copper.

Does a silver screw or terminal mean I have aluminum?

No. White-metal terminals approved Cu/Al are not aluminum: they are an alloy compatible with both metals. Only the jacket marking, or an electrician's check, tells you.

What should I do if I find it?

Have the installation checked by an electrician, then choose between fixing every connection or replacing the wiring with copper. If your lights flicker or a plate gets hot, have it checked without delay.

My dryer cable is aluminum: is that a problem?

Not in itself. Aluminum is allowed on large circuits, with a receptacle marked Cu/Al and a joint compound. This guide is mainly about the small wires of outlets and lights.